      Mobily Tier-2 Sulay is located in the area Riyadh (ar-Riya?), Saudi Arabia (Kingdom of Saudi Arabia (KSA)), and the colocation data center is carrier neutral. The data center was last updated on 21-01-2014.


      Address:
      Mobily
      Riyadh
      11423 Sulay
      Riyadh, Saudi Arabia

      » Request quote
      » Visit website

      Click here to find other data centers
      owned and operated by Mobily.


      Profile
      Tenants
      Connectivity
      Request quote
      Office space
      Rack Cabinets
      Dedicated Servers
      Suites
      Footprints
      Virtual Servers
      Cages
      Hosting of individual servers
      Remote Hands

      Profile


      MECHANICAL SYSTEM
      --------------------------

      a- Cooling System: Refrigerant cooling system.

      b- CRAH redundancy: N+1, Data Center equipment demand cooling load is 1000 W/m2

      c- Fuel Oil: Generator fuel oil storage 48 hours capacity

      d -BMS : Computerized Building Management System M&E equipment verification and management


      ELECTRICAL SYSTEM
      -------------------------
      a- Design Load: The electrical connected load is 1.2 MVA with a demand load of 0.9 MVA.

      b- Transformer: 2 x 1500 kVA Power Transformer, 380/220V, 3P, 4W, 60Hz.

      c- Generators: 3 x 2354 kVA/1883 kW Continuous Rated Generator configured in N+1

      d- Paralleling Switch gear: One set of paralleling switch gear for concurrently maintainable requirements which is controlled and monitored by Load Shedding Panel

      e- UPS: parallel redundant system in N+1 configuration, 200KVA modular units with 30 minute battery autonomy at full load. 1000 W/m2 for Data Center

      f- Rectifier System: Active + Active System, (N+N) at 200 W/m2, 1000 Ah for 2 hrs + 2hrs battery autonomy time

      g- Security System : IP access control System and Analog CCTV system


      Mobily Tier-2 Sulay Pricing/Quotes


      If you are interested in receiving a quote for Mobily, please try our free quote service.

      Copyright © Data Center Map - Sitemap
      Your guide to colocation data centers, managed hosting, cloud servers etc.
      av 国产 日韩 欧美 在线播放
      <big id="5brt0"><em id="5brt0"></em></big>
    1. <object id="5brt0"></object>
    2. <code id="5brt0"></code><code id="5brt0"></code>
    3. <th id="5brt0"><sup id="5brt0"></sup></th><pre id="5brt0"></pre>

      <code id="5brt0"></code>