      Data Center Map

      Mobily Tier-3 Dammam


      » Index » Saudi Arabia » Dammam » Mobily Tier-3 Dammam

      Mobily Tier-3 Dammam is located in the area Dammam (Ad Dammam), Saudi Arabia (Kingdom of Saudi Arabia (KSA)), and the colocation data center is carrier neutral. The data center was last updated on 21-01-2014.


      Address:
      Mobily
      Dammam
      11423 Adama
      Dammam, Saudi Arabia

      » Request quote
      » Visit website

      Click here to find other data centers
      owned and operated by Mobily.


      Profile
      Tenants
      Connectivity
      Request quote
      Office space
      Rack Cabinets
      Dedicated Servers
      Suites
      Footprints
      Virtual Servers
      Cages
      Hosting of individual servers
      Remote Hands

      Profile


      MECHANICAL SYSTEMS
      ---------------------------
      a-Cooling system: Chilled water cooling system, dual flow and return with isolating valves at each T section.4 x. air cooled water chiller for Data Center, N+1

      b- CRAH redundancy N+1, Data Center equipment demand cooling load is 1000 W/m2.

      c-Fuel Oil: Generator fuel oil storage 67 hours capacity at 100% load

      D-BMS Computerized Building Management System M&E equipment verification and management

      ELECTRICAL SYSTEMS
      --------------------------
      a-Design load: The electrical connected load is 10.75 MVA with a demand load of 9 MVA.

      b-Transformers: 8 x 2500 kVA power transformer, 380/220V, 3P, 4W 60 Hz.

      c-Generators: 5 x 2000 kVA/1600 kW Rated Diesel Generators, Design in N+1.

      d-Paralleling Switch gear: Two set of paralleling switchgear for concurrently maintainable requirements monitored and controlled by two separate Load Shedding Panel.

      e-UPS: parallel redundant system in N+N configuration, 200 KVA modular units with 30 minute battery autonomy at full load.

      f-Rectifier System Active + Active System, (N+N) at 200 W/m2, 1000 Ah for 2 hrs + 2hrs battery autonomy time.

      g-Security System: IP access control system and IP CCTV integrated with BMS for On-Off Status only as per Security Department requirement.


      Mobily Tier-3 Dammam Pricing/Quotes


      If you are interested in receiving a quote for Mobily, please try our free quote service.

      Copyright © Data Center Map - Sitemap
      Your guide to colocation data centers, managed hosting, cloud servers etc.
      av 国产 日韩 欧美 在线播放
      <big id="5brt0"><em id="5brt0"></em></big>
    1. <object id="5brt0"></object>
    2. <code id="5brt0"></code><code id="5brt0"></code>
    3. <th id="5brt0"><sup id="5brt0"></sup></th><pre id="5brt0"></pre>

      <code id="5brt0"></code>