      Data Center Map

      Kozma DC


      » Index » Hungary » Budapest » Kozma DC

      Kozma DC is located in the area Budapest, Hungary, and the colocation data center is not carrier neutral. The data center was last updated on 06-07-2010.


      Address:
      Invitel Telecommunication Inc.
      Kozma u. 2.
      1108 Budapest
      Hungary

      » Request quote
      » Visit website

      Click here to find other data centers
      owned and operated by Invitel Telecommunication Inc..


      Profile
      Tenants
      Request quote
      Office space
      Rack Cabinets
      Dedicated Servers
      Suites
      Footprints
      Virtual Servers
      Cages
      Hosting of individual servers
      Remote Hands

      Profile


      Building
      . Address: 1108 Budapest, Kozma u. 2.
      . Full size of machine room: 1,500 m?br/>. False floor load bearing capacity: point-like; 50 kN/m?br/>. Machine room's full height to ceiling, available for equipment installations: 3.7 metres
      . Fire rating: 60 minutes
      . Redundancy of power supply and building machinery (HVAC) systems: at least N + 1
      . Availability of the power supply and air conditioning services: 99.999%
      Telecomm. connections
      . Two-side, independent optical links and microwave connection to Invitel's infrastructure
      . Additional optical fibres to connect customers via optical connections
      . Direct connections to the major Internet nodes (e.g. Invitel's DataCenter in Ilka Street, BIX, Infopark, Dataplex, etc.)
      . A radio connection can also be provided to the DataCenter
      . 3x10Gbps redundant connection to Invitel's other sites
      Power Supply and Cooling
      . Availability of the power and air conditioning services: 99.999%
      . 3 medium voltage power supply lines, each 1600 kVA/10kV (2 operating, 1 standby)
      . In 2 diesel groups, 2+2 1400-kVA "Cummins Power Generation" type generators in tandem mode
      . Under full load, the system can cover a power outage of 72 hours
      . 2N UPS systems, in a "3+1" configuration on either side, performance being 1650 kVA + 550 kVA, to ensure uninterrupted power supply between the loss of power and the run-up time of generators
      . Under full load, the system can cover a power outage of 30 minutes
      . In the machine rooms, A + B independent UPSs
      . 1600 kW cooling performance, with a 2N redundancy
      . Power saving cooling solutions (a combination of free cooling condensers and compact liquid chillers)
      . 40 indoor computer air conditioners, each with a capacity of 50 kW, c/w humidity maintenance, in an N+2 number per machine room
      . Air handling units to supply fresh, dust-free, heated/cooled air to the building
      Security
      . 24/7 security service
      . Closed-chain IP video monitoring and recording system in the whole outdoor facility area, as well as in interior spaces
      . Continuously monitored pass and intrusion detection system
      . Continuously monitored building supervision system
      . Machine rooms protected against conducted and radiated electromagnetic disturbances (EMC)
      . Early warning smoke detection system with aspiration-based and optical detectors
      . Delay between fire detection and start of extinguishing : 30 seconds
      . Extinguishing system: with FM-200 (HFC-227ea) extinguishing gas


      Kozma DC Pricing/Quotes


      If you are interested in receiving a quote for Invitel Telecommunication Inc., please try our free quote service.

      Copyright © Data Center Map - Sitemap
      Your guide to colocation data centers, managed hosting, cloud servers etc.
      av 国产 日韩 欧美 在线播放
      <big id="5brt0"><em id="5brt0"></em></big>
    1. <object id="5brt0"></object>
    2. <code id="5brt0"></code><code id="5brt0"></code>
    3. <th id="5brt0"><sup id="5brt0"></sup></th><pre id="5brt0"></pre>

      <code id="5brt0"></code>